Features
- Clear flowing lamp for gas alarm.
- Automatic backup to operate under electric power failure for more than 2 weeks (350 hrs). (KS-7O and KS-7D only)
- Small and lightweight for easy installation.
- Remote sensor capability for KS-7O
Accessories
- Separate Sensor Unit KS-7OF (for KS-7O only)
- Battery Unit KS-7xB
Gases
Detectable gases |
Carbon dioxide | CO2 |
Carbon monoxide | CO |
Oxygen | O2 |
Specifications / Approvals
Model | KS-7O | KS-7D | KS-7R |
Gas Detected | Oxygen (O2) | Carbon Monoxide (CO) | Carbon Dioxide (CO2) |
Detection Range | 0 to 25.0 vol% or 0 to 50.0 vol% | 0 to 75 ppm, 0 to 150 ppm, 0 to 250 ppm, or 0 to 4000 ppm | 360 to 5000ppm |
Concentration Indication | LCD 3-digit digital, 0.1vol% resolution (with backlight) | LCD 4-digit digital, 1ppm resolution (with backlight) | LCD 4-digit digital, 5ppm resolution (with backlight) |
Alam Set Value | For 25.0vol%: 1st stage 19.0vol%, 2nd stage: 18.0vol% For 50.0vol%: 1st stage 18.0vol%, 2nd stage: 25.0vol% | For F.S. 75ppm: 25/50ppm For F.S. 150ppm: 50/100ppm For F.S. 250ppm: 50/150ppm For F.S. 400ppm: 50/150ppm | AL1: 2000ppm AL2: 5000ppm |
Alarm Indication | 1st stage: Orange LED blinks, flowing Orange status lamp 2nd stage: Red LED blinks, flowing Red status lamp Buzzer: more than 70 dB/1m |
External Output | Gas concentration analog output: 4-20m ADC Gas alarm contact for 1st and 2nd stage: 1a non-voltage Latching (standard) or non-latching |
Other Functions | Maintenance mode, alarm stop |
Operating Temperature/humidity | -10 to +40 °C / 30 to 85 %RH | -5 to +40 °C / 30 to 85 %RH | -10 to +50 °C / 0 to 85 %RH (No rapid temp. or humidity changes, no condensation) |
Power Source | 24 VDC ±10% |
Power Consumption | Monitoring: 1W, During alarm: 3W |
Dimensions | W82 x H150 x D35 mm (excluding protrusions) |
Weight | Approx. 300g |
Options | Separate Sensor Unit KS-7OF, Battery Unit KS-7xB | Battery Unit KS-7xB | |